Four Way Outlet Hydrant Stand-post

Inlet

100 NB Flange as per ANSI

Outlet

2 X 80 NB Flange as per ANSI

Outlet attachment

Oblique Valve / Hydrant Valve

Material of Construction

Pipe / Bends

Mild Steel ERW Pipes

Inlet Outlet Flange

As per ANSI / ASTM A 105 / IS 2062

Type of Testing

Parameter

Hydro Testing of Body

23 Kg/cm2(g)

Water Seat Tightness Test

18 Kg/cm2(g)

Flow testing

900 LPM for Single Outlet at 7 Kg/cm2(g)

Model No.

Description

Inlet

Outlet

Approvals

Material of

Construction

QOSP-1800-MS

Quadra Outlet Stand Post

Flanged Inet 150 mm

4 Nos. 80mm NB Flange

Hydrant ISI Marked

MS ERW Pipe
Carbon Steel